● 7505 PARTS & ACCESSORIESAdvanced Burner ControlProduct DescriptionThe Beckett GeniSys™ Advanced Burner Control is a 120 Vac primary safety control for residential and light commercial oil burners used in boiler, furnace, and water heater applications. The GeniSys is used with a suitable cad cell flame sensor to control the oil burner motor, igniter, and optional solenoid valve. It has 24 Vac thermostat terminals (if applicable) compatible with both mechanical and many power stealing thermostats.
Get Beckett 7505 Owner's manual. Get all Beckett manuals! Sign up to create an account. Motor-off delay on a 7505P will be disabled if the. It may require an isolation relay for proper operation. The Beckett A/C Ready Kit (part no. 51950U) provides.
Beckett CorporationMail: P.O. Box 1289, Elyria, OH 44036 ● Phone: 800-OIL-BURN (800-645-2876)● FAX: (440)327-1064R.W. Beckett Canada Ltd.PARTS & ACCESSORIESUnit 3 - 430 Laird Road, Guelph, Ontario, Canada N1G 3X7 ● Phone: 800-665-6972● FAX: (519)763-5656www.beckettcorp.comCross-ReferenceChartBeckett GeniSysLockoutValve-onMotor-offReplacesReplacesControl Part No.Timedelay time 2delay time 2Honeywell:Carlin:7505A 000015 sec-R7184A, R8184G48245, 0, 5B 150015 sec15 sec-R7184B-7505P 151515 sec15 sec15 secR7184P, R7184U 15P 153015 sec15 sec30 secR7184P, R7184U 15P 152M15 sec15 sec2 minR7184P, R7184U 160200 11) Beckett snap-inalarm module required for direct replacement of the control. 2) Valve-ondelay and motor-offdelay timings on all models are programmable with Beckett snap-inprogramming display. Other factory set timings are available. Contact Beckett for alternate timings.
OperationSequence of Operation19PumpStandbyprime342 Valve-onTrial forLockoutdelay5ignitionIgnitioncarryover8 Motor-off67RecycleRundelayPriming The Pump1. Initiate a call for heat.2.
When the burner starts, press and hold the reset button for 15 seconds until the yellow light turns on.3. Release the button. The yellow light will turn off and the burner will start again.4. At burner start up, click the reset button while the igniter is still on to enter Pump Prime mode. The yellow light will turn on.5. Bleed the pump until all froth and bubbles are purged.6. If necessary, repeat steps 4 and 5 until the pump is fully primed and the oil is free of bubbles.7.
![Beckett 7505 Beckett 7505](/uploads/1/2/5/4/125425584/702046258.png)
When finished, hold the reset button or remove the call for heat to exit Pump Prime mode and return to Standby. Resetting From Restricted LockoutIf the control locks out three times without a satisfied call for heat or fails the motor relay check, the Lockout becomes restricted in order to prevent repetitious resetting by the homeowner. To reset, hold the button down for 15 seconds until the red light turns off and the yellow LED turns on.Disable FunctionAny time the burner is running, press and hold the reset button to disable the burner. The burner will remain off as long as the button is held.Cad Cell Resistance IndicatorDuring the burner Run state, click the reset button to check the cad cell flame resistance range. The yellow light will flash1 to 4 times depending on the amount of light detected by the cad cell. See the table below:Yellow LED FlashesCad Cell Resistance1 Normal (0 - 400 ohms)2 Normal (400 - 800 ohms)3 Normal (800 - 1600 ohms)4 Limited (1600 ohms - Lockout).